點擊次數:559 更新時間:2021-10-20

直流高(gao)(gao)壓(ya)(ya)發生器(qi)主要適用(yong)于(yu)電(dian)(dian)力(li)、工(gong)礦、冶金以及鋼(gang)鐵等(deng)企(qi)業對其氧化(hua)鋅避(bi)雷器(qi)、電(dian)(dian)力(li)電(dian)(dian)纜、變壓(ya)(ya)器(qi)以及發電(dian)(dian)機等(deng)高(gao)(gao)壓(ya)(ya)電(dian)(dian)氣(qi)設備進行直流耐(nai)壓(ya)(ya)試驗。

直(zhi)流高壓(ya)發生器(qi)的(de)故障判(pan)斷說(shuo)明:


  1、首先(xian)將(jiang)控(kong)制箱(xiang)面(mian)板上(shang)的(de)接(jie)(jie)(jie)地端子與高(gao)(gao)壓塔的(de)接(jie)(jie)(jie)地接(jie)(jie)(jie)線(xian)柱用(yong)(yong)接(jie)(jie)(jie)地線(xian)連接(jie)(jie)(jie)在(zai)一起(qi)并與現場或試(shi)驗室的(de)地線(xian)接(jie)(jie)(jie)牢(lao),為保證您與設備(bei)的(de)安(an)全,請務必反復檢(jian)查地線(xian),確保各部(bu)接(jie)(jie)(jie)地良好,用(yong)(yong)七芯電纜連接(jie)(jie)(jie)控(kong)制箱(xiang)與高(gao)(gao)壓塔,電纜兩端為同樣的(de)快速(su)航空插頭(tou),注意用(yong)(yong)插頭(tou)側面(mian)豁口(kou)對(dui)準(zhun)插座內側粗凸部(bu)分插入并順時針擰緊,接(jie)(jie)(jie)好電源線(xian),電源為單項工頻交流220V。


  2、打(da)開(kai)電(dian)源開(kai)關(guan),此(ci)時(shi)電(dian)源開(kai)關(guan)燈和面板表亮,打(da)開(kai)高(gao)(gao)壓(ya)(ya)(ya)開(kai)關(guan),則(ze)高(gao)(gao)壓(ya)(ya)(ya)指示燈亮,如高(gao)(gao)壓(ya)(ya)(ya)提(ti)示蜂鳴(ming)器處在開(kai)的位置(zhi),則(ze)鳴(ming)叫以提(ti)示操作者在加高(gao)(gao)壓(ya)(ya)(ya),此(ci)時(shi),順(shun)時(shi)針(zhen)旋轉高(gao)(gao)壓(ya)(ya)(ya)輸出調(diao)節(jie)鈕,則(ze)升(sheng)高(gao)(gao)壓(ya)(ya)(ya),電(dian)壓(ya)(ya)(ya)表顯示為負載試品上(shang)的電(dian)壓(ya)(ya)(ya)KV值,電(dian)流(liu)(liu)表則(ze)顯示試品上(shang)流(liu)(liu)過的電(dian)流(liu)(liu)與所(suo)有泄漏電(dian)流(liu)(liu)之和但不包括內置(zhi)高(gao)(gao)壓(ya)(ya)(ya)分壓(ya)(ya)(ya)器的電(dian)流(liu)(liu),電(dian)流(liu)(liu)是微安值。


  如果打(da)(da)開電源開關(guan),并(bing)打(da)(da)開高(gao)(gao)(gao)壓開關(guan)時,高(gao)(gao)(gao)壓顯示(shi)燈(deng)不(bu)亮,且故障顯示(shi)中(zhong)“回零(ling)"燈(deng)亮時則(ze)表示(shi)高(gao)(gao)(gao)壓輸出調(diao)節(jie)鈕(niu)未在(zai)零(ling)位,國電西(xi)高(gao)(gao)(gao)建議將逆時針旋鈕(niu)至“回零(ling)"燈(deng)滅(mie),再順時針調(diao)節(jie)即可升(sheng)壓。


  3、直(zhi)流高(gao)(gao)壓(ya)(ya)(ya)(ya)發生器若不(bu)需要額定(ding)(ding)輸出(chu)電壓(ya)(ya)(ya)(ya)范(fan)(fan)圍(wei)內(nei)的(de)(de)調壓(ya)(ya)(ya)(ya)保護(hu)(hu)(hu)時(shi),要把過壓(ya)(ya)(ya)(ya)保護(hu)(hu)(hu)整定(ding)(ding)鈕(niu)順時(shi)針(zhen)(zhen)旋(xuan)至(zhi)大值,此時(shi),當(dang)輸出(chu)電壓(ya)(ya)(ya)(ya)超過額定(ding)(ding)輸出(chu)電壓(ya)(ya)(ya)(ya)時(shi)即自動保護(hu)(hu)(hu),切斷高(gao)(gao)壓(ya)(ya)(ya)(ya),若要求(qiu)在額定(ding)(ding)輸出(chu)電壓(ya)(ya)(ya)(ya)范(fan)(fan)圍(wei)內(nei)進行調壓(ya)(ya)(ya)(ya)保護(hu)(hu)(hu)時(shi),請空載升(sheng)(sheng)壓(ya)(ya)(ya)(ya)按(an)以上步驟升(sheng)(sheng)壓(ya)(ya)(ya)(ya)到(dao)預定(ding)(ding)的(de)(de)保護(hu)(hu)(hu)電壓(ya)(ya)(ya)(ya)上,再將過壓(ya)(ya)(ya)(ya)保護(hu)(hu)(hu)整定(ding)(ding)旋(xuan)鈕(niu)慢(man)慢(man)逆(ni)時(shi)針(zhen)(zhen)旋(xuan)轉(zhuan)到(dao)所需要的(de)(de)電壓(ya)(ya)(ya)(ya)上,作過壓(ya)(ya)(ya)(ya)保護(hu)(hu)(hu)動作,“過壓(ya)(ya)(ya)(ya)"指示(shi)燈亮,保持過壓(ya)(ya)(ya)(ya)保護(hu)(hu)(hu)整定(ding)(ding)旋(xuan)鈕(niu)定(ding)(ding)于此位置(zhi),將升(sheng)(sheng)壓(ya)(ya)(ya)(ya)旋(xuan)鈕(niu)回到(dao)零位上,關閉電源,接上試品,則以后(hou)升(sheng)(sheng)壓(ya)(ya)(ya)(ya)超過預定(ding)(ding)電壓(ya)(ya)(ya)(ya)時(shi)即切斷高(gao)(gao)壓(ya)(ya)(ya)(ya)。


  4、直流高壓(ya)發生器負(fu)載為大容性負(fu)載時,為避(bi)免充電(dian)電(dian)流過大而觸發過流保護,請(qing)適當放慢升壓(ya)速(su)度(du),試驗完畢后,將輸(shu)出電(dian)壓(ya)調(diao)整鈕逆(ni)時針旋至(zhi)零位(wei),關閉高壓(ya)開關,此(ci)時電(dian)壓(ya)表仍顯示試品上(shang)的電(dian)壓(ya)值,請(qing)等試品通過高壓(ya)塔(ta)放電(dian)至(zhi)20KV以下時再(zai)用(yong)接地棒放電(dian),以確保安全!


  5、當(dang)發(fa)生過壓(ya)、過流等故障時,高(gao)壓(ya)自動切斷,高(gao)壓(ya)顯示(shi)燈(deng)(deng)滅,蜂嗚器停(ting)止鳴叫,相應故障指示(shi)燈(deng)(deng)亮,說(shuo)明是品已短路,若要重新啟動時,應將高(gao)壓(ya)輸(shu)出(chu)調整鈕回零位,微調旋(xuan)鈕同(tong)樣在零位上,再關(guan)電(dian)源開(kai)關(guan),然后再打開(kai)電(dian)源開(kai)關(guan)才能(neng)切除保護重新升壓(ya)。


  △ 正常工作關(guan)機(ji)時,應先將高壓調整旋鈕(niu)逆時回到零(ling)位(wei)上,再將微調旋鈕(niu)回到零(ling)位(wei)上,后關(guan)閉電源開關(guan)。

  △ 電源開(kai)關(guan)(guan)兼用于保護(hu)重置(zhi)開(kai)關(guan)(guan),當故障顯(xian)示燈(回零(ling)顯(xian)示燈除外)亮后應關(guan)(guan)閉電源開(kai)關(guan)(guan)再打開(kai)才(cai)能(neng)解除保護(hu),重新升壓。